Short description
I/O module | 4 safe type A digital inputs, 4 pulse outputs, 24 VDC |
General information
Safety characteristics
I/O power supply
Nominal voltage | 24 VDC |
Voltage range | 24 VDC -15% / +20% |
Integrated protection | Reverse polarity protection |
Safe digital inputs
Pulse outputs
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | 0 to 2000 m, no limitation |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | 0 to 60°C |
Vertical mounting orientation | 0 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately. |
Pitch | 25+0.2 mm |
物料号:
X20SI4100描述:
- 4 safe digital inputs
- 4 pulse outputs
- Sink circuit
- Software input filter configurable for each channel
This module is equipped with 4 safe digital inputs. It is designed for a nominal voltage of 24 VDC.
The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3.
The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.
This module is designed for X20 12-pin terminal blocks.
必备附件
Automation Studio硬件升级 | 版本(日期) | 下载 |
---|---|---|
V3.0 HW Upgrade (X20SI4100) | EXE / 3 MB | |
V4.0 HW Upgrade (X20SI4100) | EXE / 3 MB | |
V4.6 HW Upgrade (X20SI4100) | EXE / 2 MB | |
V6.0 HW Upgrade (X20SI4100) | EXE / 2 MB |
E-CAD(电子或EPLAN模板) | 版本(日期) | 下载 |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD(机械模板) | 版本(日期) | 下载 |
---|---|---|
3D file STEP X20(c)Sxxxxx - Terminal block right side | ZIP / 21 KB | |
DFX File I/O Slice | ZIP / 4 KB | |
Dimensions PDF X20 I/O Slice | PDF / 45 KB |
工具/实用程序/ 示例 | 版本(日期) | 下载 |
---|---|---|
Sistema library | ZIP / 336 KB |