Short description
Hub | 2 Fast Ethernet interfaces for fiber optic cables for redundant wiring |
General information
Status indicators | Module status, bus function |
Diagnostics | |
Module status | Yes, using LED status indicator |
Bus function | Yes, using LED status indicator |
Power consumption | 2.3 W (rev. <D0: 2.8 W) |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
KC | Yes |
Interfaces
Type | Active hub expansion module |
Variant | 2x female duplex LC |
Transfer rate | 100 Mbit/s |
Transfer | |
Physical layer | 100BASE-FX |
Half-duplex | Yes |
Full-duplex | No |
Autonegotiation | No |
Auto-MDI/MDIX | No |
Hub propagation delay | 0.96 to 1 µs |
Wave length |
Typ. 1300 nm Rx range: 1270 to 1380 nm Tx range: 1270 to 1380 nm
|
Cable fiber type |
Multimode fiber with 62.5/125 µm or 50/125 µm core diameter On both sides: Male duplex LC connector |
Optical power budget | |
Glass fiber 62.5/125 µm, NA = 0.275 | 11 dB |
Glass fiber 50/125 µm, NA = 0.200 | 7.7 dB |
Line length | |
Half-duplex | Max. 400 m between 2 stations (segment length) |
POWERLINK | Max. 2 km between 2 stations (segment length) |
Electrical properties
Electrical isolation | Power supply isolated from Ethernet (IF1 and IF2) |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation (with ≥2 hubs) | -25 to 50°C (Rev. <D0: 0 to 40°C) |
Vertical mounting orientation (with ≥2 hubs) | -25 to 35°C (Rev. <D0: 0 to 35°C) |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
物料号:
X20HB2886描述:
- Active hub expansion module
- 2x 100 BASE-FX hub for redundant wiring
- Hot-swap-capable
The X20BC8084 POWERLINK bus controller and the X20HB8884 module are equipped with an integrated link selector function. An additional 1 or 2 slots are available, depending on the bus base used. The active X20HB2886 hub expansion module can be operated in these slots. Note that the hardware revision of the X20BC8084 and the X20HB8884 must be ≥E0.
The active hub expansion module is equipped with one integrated 2x hub and allows redundant wiring. This means that the connection between the two 100 Base-FX interfaces remains intact if there is a failure in the bus controller or Compact Link Selector. The Ethernet connection is made using 62.5/125 μm or 50/125 µm fiber optic multimode cable with a duplex LC connection. The status of the module and network are indicated by LEDs.
更多信息:
Technology information: 冗余
User's manual: Redundancy for control systems
必备附件
Expandable bus controllers
X20BC8084 | X20 bus controller, 1 POWERLINK interface, 1x link selector for POWERLINK cable redundancy, supports expansion with active X20 hub modules, 2x RJ45, order bus base, power supply module and terminal block separately! |
System modules for expandable bus controllers
X20BB82 | X20 bus base, for X20 base module (BC, HB, etc.) and X20 power supply module, with 2 expansion slots for 2 X20 add-on modules (IF, HB, etc.), X20 end cover plates (left and right) X20AC0SL1/X20AC0SR1 included |
X20 redundancy systems
X20HB8884 | X20 Compact link selector, 2x RJ45, order bus base, power supply module and terminal block separately! |
Automation Studio硬件升级 | 版本(日期) | 下载 |
---|---|---|
V4.0 HW Upgrade (X20HB2886) | EXE / 827 KB |
E-CAD(电子或EPLAN模板) | 版本(日期) | 下载 |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD(机械模板) | 版本(日期) | 下载 |
---|---|---|
3D File DXF/STEP X20 system module X20(c)HB288x | ZIP / 1 MB |