B&R ID code
|
0x2009
|
System requirements
|
|
Automation Studio
|
3.0.71 or later
|
Automation Runtime
|
2.95 or later
|
SafeDESIGNER
|
2.58 or later
|
Safety Release
|
1.1 or later
|
mapp Technology Package
|
mapp Safety 5.7.0 or later
|
Status indicators
|
I/O function per channel, operating state, module status
|
Diagnostics
|
|
Module run/error
|
Yes, using LED status indicator and software
|
Outputs
|
Yes, using LED status indicator and software
|
Blackout mode
|
|
Scope
|
Module
|
Function
|
Module functionality
|
Standalone mode
|
No
|
Max. I/O cycle time
|
800 µs
|
Power consumption
|
|
Bus
|
0.25 W
|
Internal I/O
|
0.98 W
|
Additional power dissipation caused by actuators (resistive) [W]
|
1.92
|
Electrical isolation
|
|
Channel - Bus
|
Yes
|
Channel - Channel
|
No
|
Certifications
|
|
CE
|
Yes
|
UKCA
|
Yes
|
Functional safety
|
cULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013
|
Functional safety
|
IEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3
|
Functional safety
|
EN 50156-1:2004
|
ATEX
|
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
|
UL
|
cULus E115267 Industrial control equipment
|
HazLoc
|
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
|
DNV
|
Temperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
|
CCS
|
Yes
|
LR
|
ENV1
|
KR
|
Yes
|
ABS
|
Yes
|
BV
|
EC21B Temperature: 5 - 45°C Vibration: 0.7 g EMC: Bridge and open deck
|
KC
|
Yes
|