Permissible network configurations
|
TT, TN
|
Mains input voltage
|
1x 110 - 230 VAC ±10% 3x 200 - 480 VAC ±10%
|
Frequency
|
50/60 Hz ±5%
|
SCCR
|
5 kA
|
Mains fuse protection
|
Max. 45 A (gG per IEC 60269-1 or class J non-delayed per UL 248-8) Max. 36 A (class J time-delayed per UL 248-8) Max. 32 A (LS per IEC 60947-2 characteristic C or UL 489)
|
Continuous current
|
16 Aeff
|
Peak current
|
24 Aeff
|
Reduction of continuous current depending on ambient temperature
|
|
Starting at 50°C
|
0.32 Aeff/K
|
Reduction of continuous current depending on installation elevation
|
|
Starting at 1000 m above sea level
|
0.8 Aeff per 1000 m
|
Power dissipation
|
Typ. 10.8 W
|
Line filter per EN 61800-3, category C3
|
Yes
|
Variant
|
|
L1, L2, L3 and L1´, L2´, L3´
|
Terminals
|
PE
|
M5 threaded bolt
|
Shield connection
|
|
On mains
|
No
|
On device
|
No
|
Terminal connection cross section
|
|
Flexible and fine-stranded wires
|
|
With wire end sleeve
|
0.5 to 6 mm² 20 - 8 AWG
|