Short description
I/O module 2 analog outputs ±10 V or 0 to 20 mA / 4 to 20 mA
General information
B&R ID code 0x1BA2
Status indicators I/O function per channel, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Channel type Yes, using software
Power consumption
Bus 0.01 W
Internal I/O 1.1 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
CCS Yes
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
KC Yes
Analog outputs
Output ±10 V or 0 to 20 mA / 4 to 20 mA, via different terminal connections
Max. output current 10 mA at voltage >5 V
15 mA at voltage <5 V
Digital converter resolution
Voltage ±12-bit
Current 12-bit
Conversion time 200 µs for all outputs
Settling time on output change over entire range 1 ms
Switch on/off behavior Internal enable relay for startup
Max. error
Gain ±0.15%
Offset ±0.05%
Voltage
Gain ±0.15%
Offset ±0.05%
Current
Gain ±0.15%
Offset ±0.05%
Output protection Short-circuit proof
Output format
Voltage INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
Current INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
Load per channel
Voltage Max. ±10 mA, load ≥1 kΩ
Current Load max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0)
Short-circuit proof Current limiting ±40 mA
Output filter First-order low-pass filter / cutoff frequency 10 kHz
Max. gain drift ±0.02%/°C
Max. gain drift
Voltage ±0.02%/°C
Current ±0.02%/°C
Max. offset drift ±0.032%/°C
Max. offset drift
Voltage ±0.032%/°C
Current ±0.032%/°C
Error caused by load change
Voltage Max. 0.11%, from 10 MΩ → 1 kΩ, resistive
Current Max. 0.5%, from 1 Ω → 600 Ω, resistive
Nonlinearity <0.007%
Insulation voltage between channel and bus 500 Veff
Electrical properties
Electrical isolation Channel isolated from bus
Channel not isolated from channel
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB06 or X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch 12.5+0.2 mm
Materiaalnummer:
X20AO2622
Omschrijving:
  • 2 analog outputs
  • Either current or voltage signal possible
  • 13-bit digital converter resolution

The module is equipped with 2 outputs with 13-bit (including sign) digital converter resolution. It is possible to select between the current and voltage signal using different terminals.

This module is designed for X20 6-pin terminal blocks. If needed (e.g. for logistical reasons), the 12-pin terminal block can also be used.

Vereiste toebehoren
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O power supply connected through
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O power supply connected through
Terminal blocks
X20TB06 X20 terminal block, 6-pin, 24 VDC keyed
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Automation Studio HW Upgrades Versie (Datum) Download
V2.6 HW Upgrade (X20AO2622) EXE / 953 KB
V3.0 HW Upgrade (X20AO2622) EXE / 1 MB
V4.0 HW Upgrade (X20AO2622) EXE / 738 KB
Certificaten Versie (Datum) Download
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 MB
BV Type Approval Certificate - X20 PDF / 556 KB
CCS Type Approval Certificate - X20 PDF / 285 KB
DNV Type Approval Certificate - X20 PDF / 194 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 502 KB
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 MB
Safe cutoff of potential groups PDF / 211 KB
UK Declaration PLC X20 PDF / 151 KB
X20, X67 KC certificates PDF / 6 MB
Documentatie Versie (Datum) Download
Data sheet X20AO2622 PDF / 385 KB
Installation- / EMC-Guide PDF / 20 MB
X20 Package leaflet ATEX/CSA PDF / 2 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Electro of EPLAN Templates) Versie (Datum) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. Templates) Versie (Datum) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Graag land en taal kiezen

B&R Logo