Short description
Communication module | ASi interface master |
General information
B&R ID code | 0xA718 |
Status indicators | Module status, network status, data transfer |
Diagnostics | |
Module status | Yes, using LED status indicator and software |
Network status | Yes, using LED status indicator and software |
Data transfer | Yes, using LED status indicator |
Fieldbus current consumption | Max. 27 mA |
Power consumption | |
Bus | 1.1 W |
Fieldbus | 0.85 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
CCS | Yes |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
KC | Yes |
Interfaces
Electrical properties
Electrical isolation | PLC isolated from AS (IF1) |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order 1x terminal block TB704 separately. |
Slot | In the X20 PLC and expandable bus controller X20BC1083 |
型番:
X20IF10A1-1説明:
- ASi interface master
- Electrically isolated
- 4-pin bus connector
The interface module is equipped with an ASi master interface. This allows third-party components to be integrated in the B&R system and makes it possible to quickly and easily transfer data in both directions.
The interface module can be operated in X20 CPUs or in the expandable POWERLINK bus controller X20BC1083.
必須アクセサリ
Automation Studio HW アップグレード | バージョン (日付) | ダウンロード |
---|---|---|
V3.0 HW Upgrade (X20IF10A1-1) | EXE / 1 MB | |
V4.0 HW Upgrade (X20IF10A1-1) | EXE / 3 MB |
E-CAD(ElectroまたはEPLANテンプレート) | バージョン (日付) | ダウンロード |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD (Mechan.Templates) | バージョン (日付) | ダウンロード |
---|---|---|
3D File DXF/STEP X20 Interface module X20IF1091/10A1-1 | ZIP / 26 KB | |
Dimensions PDF X20 Interface Module X20IF1091/10A1-1 | PDF / 4 KB |
ドキュメンテーション | バージョン (日付) | ダウンロード |
---|---|---|
Data sheet X20IF10A1-1 | PDF / 1 MB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
X20 System User´s Manual | PDF / 7 MB |