Short description
Communication module | 1x POWERLINK (V1/V2) managing or controlled node |
General information
B&R ID code | 0x1F1F |
Status indicators | Module status, bus function |
Diagnostics | |
Module status | Yes, using LED status indicator and software |
Bus function | Yes, using LED status indicator and software |
Power consumption | 2 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
CCS | Yes |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
KC | Yes |
Interfaces
Electrical properties
Electrical isolation | PLC isolated from POWERLINK (X1 and X2) |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Slot | In the X20 PLC |
型番:
X20IF1082説明:
- POWERLINK for real-time Ethernet communication
- Integrated hub for efficient cabling
- Configurable ring redundancy
The interface module can be used to expand the X20 CPU for specific applications. It is equipped with an POWERLINK interface.
The interface has two RJ45 sockets. Both connections lead to an integrated hub. This makes it easy to create daisy-chain connections using POWERLINK.
詳しい情報:
Technology information: Redundancy
User's manual: Redundancy for control systems
Automation Studio HW アップグレード | バージョン (日付) | ダウンロード |
---|---|---|
V2.7 HW Upgrade (X20IF1082) | EXE / 572 KB | |
V2.7 HW Upgrade (X20IF1082) | EXE / 1 MB | |
V3.0 HW Upgrade (X20IF1082) | EXE / 2 MB | |
V4.0 HW Upgrade (X20IF1082) | EXE / 1 MB |
E-CAD(ElectroまたはEPLANテンプレート) | バージョン (日付) | ダウンロード |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD (Mechan.Templates) | バージョン (日付) | ダウンロード |
---|---|---|
3D File STEP/DXF X20BC and X20IF Module | ZIP / 1 MB |