Fuse
|
Yes, for mains, battery, battery charger
|
Deep discharge protection
|
Yes, cutoff threshold 21 VDC
|
Reverse polarity protection
|
Yes, for mains and battery
|
Short-circuit proof
|
Yes
|
Overvoltage category per EN 61131-2
|
II
|
Output during battery operation
|
|
Voltage range
|
21 to 26.8 VDC (40°C) or 28.2 VDC (0°C)
|
Rated voltage value
|
24 VDC
|
Max. output current
|
8 A (load side)
|
Power failure bypass
|
Max. 20 minutes at 150 W load (with battery 9A0100.12, 24 V / 7.2 Ah)
|
Switching threshold for mains/battery operation
|
18 V at 20 to 30 VDC input 21.5 V at 23.5 to 30 VDC input
|
Output during mains operation
|
|
Voltage range
|
20 to 30 VDC or 23.5 - 30 VDC depending on the set changeover threshold
|
Rated voltage value
|
24 VDC
|
Max. output current
|
8 A
|
Input during mains operation
|
|
Power failure bypass
|
Max. 20 min at 150 W load
|
Voltage range
|
20 to 30 VDC at a switching threshold of 18 V 23.5 to 30 VDC at a switching threshold of 21.5 V
|
Rated voltage value
|
24 VDC
|
Switching threshold for rechargeable battery
|
18 V
|
Battery charging data
|
|
Charging clearing voltage
|
27.6 VDC
|
Charging current
|
From 0.88 A to 2.88 A depending on type
|