Short description
I/O module IO-Link master with 4 IO-Link interfaces
General information
B&R ID code 0xF9F7
Status indicators -
Diagnostics
Module run/error Yes, using software status
Power consumption
Internal I/O 0.6 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
Sensor/Actuator power supply
Voltage I/O power supply minus voltage drop for short-circuit protection
Voltage drop for short-circuit protection at 0.3 A Max. 0.3 V
Power consumption Max. 12 W per IO-Link interface
Short-circuit proof Yes
Overload protection
Switch-off delay Configurable using software
Switch-off duration Configurable using software
IO-Link in master mode
Transfer rates
COM1 4.8 kbaud
COM2 38.4 kbaud
COM3 230.4 kbaud
Limit values for COM3
Max. connection capacity 22 nF (cable + IO-Link device)
Max. load 96 Ω / 250 mA
Data format 1 start bit, 8 data bits, 1 parity bit (even), 1 stop bit
Bus level 24 VDC (active), 0 VDC (resting voltage)
IO-Link in master mode or in SIO mode "digital output"
Variant Bipolar, positive and negative switching
Peak short-circuit current <1.3 A
Residual voltage <0.7 VDC at nominal current 0.25 A
Switching voltage I/O power supply minus voltage drop for short-circuit protection and semiconductor switch
Voltage drop on semiconductor switch Max. 0.44 VDC at 0.2 A
Switching frequency Typ. 25 kHz
300 kHz in IO-Link master mode
Switching delay
0 → 1 <1 µs
1 → 0 <1 µs
Switch-on in the event of overload shutdown or short-circuit shutdown Configurable with software
IO-Link in SIO mode "Digital output"
Nominal voltage 24 VDC
Nominal output current 0.25 A
Total nominal current Max. 1 A
Output circuit Sink or source
Switching frequency (resistive load) Max. 500 Hz
Output protection Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads
IO-Link in SIO mode "digital input"
Nominal voltage 24 VDC
Input characteristics per EN 61131-2 Type 1
Input filter
Hardware 220 ns
Software 3 µs (without glitch filter)
4.2 µs (with glitch filter)
Input circuit Sink
Input voltage 24 VDC -15% / +20%
Input current at 24 VDC Typ. 5.8 mA
Input resistance Typ. 4.14 kΩ
Switching threshold
Low <5 VDC
High >15 VDC
Electrical properties
Electrical isolation Bus isolated from IO-Link
IO-Link not isolated from IO-Link
Operating conditions
Mounting orientation
Any Yes
Degree of protection per EN 60529 Up to IP69K
Ambient conditions
Temperature
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 100%, condensing
Storage 5 to 100%, condensing
Transport 5 to 100%, condensing
Mechanical properties
Dimensions
Width 47 mm
Length 95 mm
Numero materiale:
X90DSI00.04-00
Descrizione:
  • 18 to 30 VDC
  • 4 IO-Link devices
  • 4 digital channels, can be used as inputs or outputs
  • Sensor/actuator power supply
  • NetTime timestamps: IO-Link data
  • X2X Link

The DS option board is an IO-Link master that allows intelligent sensors and actuators to be connected per the IO-Link standard. Communication to the mainboard is made possible via X2X Link.

Aggiornamenti HW di Automation Studio Versione (data) Download
V4.7 HW Upgrade (X90DSI00.04-00) EXE / 3 MB
Certificati Versione (data) Download
EU Declaration Industrial sector X90 PDF / 163 KB
EU Declaration Mobile machinery X90 PDF / 146 KB
UK Declaration Industrial sector X90 PDF / 110 KB
UN ECE-R10 PDF / 382 KB
Documentazione Versione (data) Download
Data sheet X90DSI00.04-00 PDF / 1 MB
X90 mobile System User´s Manual PDF / 49 MB
E-CAD (Electro o EPLAN Template) Versione (data) Download
Makro-/Artikeldaten 4.0.1 (X90DSI00.04-00) EXE / 946 KB
X90 EPLAN P8 from V2.4 EXE / 69 MB

Si prega di scegliere il Paese e la lingua

B&R Logo