Short description
I/O module | 6 digital inputs 24 VDC for 1- or 2-wire connections |
General information
B&R ID code | 0xE222 |
Status indicators | I/O function per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Power consumption | |
Bus | 0.15 W |
Internal I/O | 0.88 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
Digital inputs
Nominal voltage | 24 VDC |
Input characteristics per EN 61131-2 | Type 1 |
Input voltage | 24 VDC -15% / +20% |
Input current at 24 VDC | Typ. 3.75 mA |
Input circuit | Sink |
Input filter | |
Hardware | ≤100 μs |
Software | Default 1 ms, configurable between 0 and 25 ms in 0.2 ms increments |
Connection type | 1- or 2-wire connections |
Input resistance | Typ. 6.4 kΩ |
Switching threshold | |
Low | <5 VDC |
High | >15 VDC |
Insulation voltage between channel and bus | 500 Veff |
Sensor power supply
Voltage | Module power supply minus voltage drop for short-circuit protection |
Voltage drop for short-circuit protection at 500 mA | Max. 2 VDC |
Summation current | 0.5 A |
Short-circuit proof | Yes |
Electrical properties
Electrical isolation |
Channel isolated from bus Channel not isolated from channel |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Starting temperature | Yes, -40°C |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | Up to 100%, condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB06 or X20TB12 separately. Order 1x bus module X20cBM11 separately. |
Pitch | 12.5+0.2 mm |
Référence produit:
X20cDI6371Description:
- 6 digital inputs
- Sink connection
- 2-wire connections
- 24 VDC for sensor supply
- Software input filter can be configured for entire module
- 1-wire connection type with 6-pin terminal block
The module is equipped with 6 inputs for 1 or 2-wire connections. The X20 6-pin terminal block can be used for universal 1-line wiring. Two-line wiring can be implemented using the 12-pin terminal block. The inputs on the module are designed for sink connections.
Accessoires obligatoires
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V3.0 HW Upgrade (X20cDI6371) | EXE / 800 KB | |
V4.0 HW Upgrade (X20cDI6371) | EXE / 666 KB |
Documentation | Version (date) | Téléchargement |
---|---|---|
Coated modules | PDF / 62 KB | |
Datasheet X20(c)DI6371 | PDF / 813 KB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
X20 System User´s Manual | PDF / 7 MB |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 KB | |
3D File STEP X20 I/O-Slice | ZIP / 872 KB | |
Dimensions PDF X20 Electronic module | PDF / 3 KB |