Short description
I/O module | 4 inputs for potentiometer displacement gauge |
General information
B&R ID code | 0x9957 |
Status indicators | Channel status, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Input | Yes, using LED status indicator and software |
Connection type | |
X2X Link | M12, B-coded |
Inputs | 4x M12, A-coded |
I/O power supply | M8, 4-pin |
Power consumption | |
Bus | 0.75 W |
Internal I/O | 2 W |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
KC | Yes |
I/O power supply
Nominal voltage | 24 VDC |
Voltage range | 18 to 30 VDC |
Integrated protection | Reverse polarity protection |
Potentiometer power supply
Short-circuit proof | Yes |
Potentiometer supply voltage Upot | 4.5 V / Max. 50 mA |
Voltage drop for short-circuit protection at 50 mA | Max. 0.13 VDC |
Potentiometer, displacement gauge
Input type | Single-ended input in the range of 0 to Upot |
Digital converter resolution | 15-bit |
Measurement sensor | 0.5 to 10 kΩ, potentiometer |
Conversion time | <200 µs for all channels |
Output format | INT (16-bit 2s complement) |
Short-circuit protection Upot | Yes |
Influence of cable length | Twisted and shielded conductors, cable length as short as possible, cable routing separate from load circuits, without intermediate terminal to sensor |
Common-mode range | 0 to Upot |
Insulation voltage between input and bus | 500 Veff |
Quantization; LSB value (14-bit) | 275 µV |
Conversion procedure | Sample & Hold |
Output of digital value | |
Open circuit on GND | 0x7FFF |
Open circuit on slider | 0x7FFF |
Open circuit on Upot | 0x0000 |
Valid range of values | 0x0000 - 0x7FFF |
Input filter | |
Cutoff frequency | 10 kHz |
Slope | 60 dB/Dec. |
Electrical properties
Electrical isolation | Bus isolated from analog input |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP67 |
Ambient conditions
Temperature | |
Operation | -25 to 60°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Mechanical properties
Dimensions | |
Width | 53 mm |
Height | 85 mm |
Depth | 42 mm |
Weight | 195 g |
Torque for connections | |
M8 | Max. 0.4 Nm |
M12 | Max. 0.6 Nm |
Référence produit:
X67AI4850Description:
- 4 inputs for potentiometer displacement gauge
The module is a 4-channel analog input module. It is used to evaluate potentiometer displacement gauges.
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V2.6 HW Upgrade (X67AI4850) | EXE / 1 Mo | |
V3.0 HW Upgrade (X67AI4850) | EXE / 458 Ko | |
V3.0 HW Upgrade (X67AI4850) | EXE / 2 Mo | |
V4.0 HW Upgrade (X67AI4850) | EXE / 2 Mo |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X67AI4850 | PDF / 590 Ko | |
X67 System User´s Manual | PDF / 6 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X67 EPLAN P8 from V2.4 | EXE / 105 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X67 | ZIP / 4 Mo |