Short description
Communication module | 1x X2X Link master |
General information
B&R ID code | 0x2525 |
Status indicators | Module status, data transfer |
Diagnostics | |
Module status | Yes, using LED status indicator |
Data transfer | Yes, using LED status indicator |
Power consumption | 1.29 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
KC | Yes |
Interfaces
Interface IF1 | |
Fieldbus | X2X Link master |
Variant | 4-pin male multipoint connector |
Number of stations | Max. 253 |
Internal bus power supply | No |
Network topology | Line |
Distance between 2 stations | Max. 100 m |
Bus terminating resistor | Internal |
Electrical properties
Electrical isolation | PLC isolated from X2X Link (IF1) |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order 1x terminal block TB704 separately. |
Slot | In expandable bus controller X20BC1083-1 |
Référence produit:
X20IF1091-1Description:
- X2X Link connection
The interface module is operated in the X20BC1083 expandable bus controller. It is equipped with an X2X Link master interface.
Accessoires obligatoires
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V2.6 HW Upgrade (X20IF1091-1) | EXE / 520 Ko | |
V2.6 HW Upgrade (X20IF1091-1) | EXE / 1 Mo | |
V3.0 HW Upgrade (X20IF1091-1) | EXE / 520 Ko | |
V3.0 HW Upgrade (X20IF1091-1) | EXE / 1 Mo | |
V4.0 HW Upgrade (X20IF1091-1) | EXE / 1 Mo |
Documentation | Version (date) | Téléchargement |
---|---|---|
Datasheet X20IF1091-1 | PDF / 148 Ko | |
Installation- / EMC-Guide | PDF / 20 Mo | |
X20 Package leaflet ATEX/CSA | PDF / 2 Mo | |
X20 System User´s Manual | PDF / 7 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 Mo |
M-CAD (modèles mécaniques) | Version (date) | Téléchargement |
---|---|---|
3D File DXF/STEP X20 Interface module X20IF1091/10A1-1 | ZIP / 26 Ko | |
Dimensions PDF X20 Interface Module X20IF1091/10A1-1 | PDF / 4 Ko |