Short description
Communication module ASi interface master
General information
B&R ID code 0xA718
Status indicators Module status, network status, data transfer
Diagnostics
Module status Yes, using LED status indicator and software
Network status Yes, using LED status indicator and software
Data transfer Yes, using LED status indicator
Fieldbus current consumption Max. 27 mA
Power consumption
Bus 1.1 W
Fieldbus 0.85 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
CCS Yes
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
KC Yes
Interfaces
Interface IF1
Fieldbus ASi interface master
Type ASi master profile M4
Variant 4-pin male multipoint connector
Power supply ASi power supply
Voltage range 24 to 32 V
Controller netX100
Max. number of slaves 62
Max. distance
Standard 100 m
With additional components 500 m
Max. cycle time 5 ms
Response time Typ. 3 ms
Electrical properties
Electrical isolation PLC isolated from AS (IF1)
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block TB704 separately.
Slot In the X20 PLC and expandable bus controller X20BC1083
Référence produit:
X20IF10A1-1
Description:
  • ASi interface master
  • Electrically isolated
  • 4-pin bus connector

The interface module is equipped with an ASi master interface. This allows third-party components to be integrated in the B&R system and makes it possible to quickly and easily transfer data in both directions. 

The interface module can be operated in X20 CPUs or in the expandable POWERLINK bus controller X20BC1083.

Accessoires obligatoires
Terminal blocks
0TB704.9 Accessory terminal block, 4-pin, screw clamp terminal block 2.5 mm²
0TB704.91 Accessory terminal block, 4-pin, push-in terminal block 2.5 mm²
Automation Studio HW Upgrades Version (date) Téléchargement
V3.0 HW Upgrade (X20IF10A1-1) EXE / 1 Mo
V4.0 HW Upgrade (X20IF10A1-1) EXE / 3 Mo
Certifications Version (date) Téléchargement
244665 CSA HazLoc CoC X20, X67 PDF / 158 Ko
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 Mo
ASi (X20IF10A1-1) PDF / 136 Ko
BV Type Approval Certificate - X20 PDF / 556 Ko
CCS Type Approval Certificate - X20 PDF / 285 Ko
DNV Type Approval Certificate - X20 PDF / 194 Ko
E115267 UL CoC X20 PDF / 1 Mo
EU Declaration ATEX X20 PDF / 218 Ko
EU Declaration of conformity PLC X20 PDF / 169 Ko
FTZU 09 ATEX 0083X PDF / 771 Ko
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 Ko
Lloyds Register PDF / 502 Ko
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 Mo
UK Declaration PLC X20 PDF / 151 Ko
X20, X67 KC certificates PDF / 6 Mo
Documentation Version (date) Téléchargement
Data sheet X20IF10A1-1 PDF / 1 Mo
Installation- / EMC-Guide PDF / 20 Mo
X20 Package leaflet ATEX/CSA PDF / 2 Mo
X20 System User´s Manual PDF / 7 Mo
E-CAD (modèles Electro ou EPLAN) Version (date) Téléchargement
X20 EPLAN P8 from V2.4 EXE / 160 Mo
M-CAD (modèles mécaniques) Version (date) Téléchargement
3D File DXF/STEP X20 Interface module X20IF1091/10A1-1 ZIP / 26 Ko
Dimensions PDF X20 Interface Module X20IF1091/10A1-1 PDF / 4 Ko

Veuillez sélectionner un pays et une langue

B&R Logo