2.6.0.1 * 05/03/2024 5 Mo EXE AS4_HW_X20SLX806.exe
Description V4.6 HW Upgrade (X20SLX806)

Revision information X20SLX806

Version 2.6.0.1:

ID: 780160
Correction of the input filter with set "Filter off".
Correction of the input filter, if a "Filter off" is set and a channel error is detected.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 780245
New data sheet V2.20
For changes see chapter "Version history" in the data sheet.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 780415 / Support ID: 400412437
Configuration for Power Calculation available
The Configuration for Power Calculation is now available in Automation Studio
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(593), 11\61968_1.fw(593)

Version 2.4.3.0:

ID: 763720 / Support ID: 400394920
SafeDomain to SafeDomain communication with differing "Process data transfer rate" setting
SafeDomain to SafeDomain communication could not be established if "Processdata transfer rate" setting differed between Managing and Connected SafeDomain.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\61968_1.fw(592), 11\61968_1.fw(592)

Version 2.4.2.0:

ID: 673420 / Support ID: 400370828, 400378297
Safe Commissioning Options without SAFEBOOL
Logger message "external machine options discrepancy" was triggered by mistake when Safe Commissioning Options where used without using any channel SafeCommissioningOptionsBITxxx
(fix available for AR >= B4.92)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 673735
"CLEAR DATA" Safe Commissioning Options
"CLEAR DATA" did not delete the data for Safe Commissioning Options with data types SAFEINT, SAFEDINT and SAFEDWORD (fix available for AR >= B4.92).
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 725975
logger messages "Inconsistent UDID files" / "Set-to-operational for unacknowledged UDID"
Fix -1073552872 "Inconsistent UDID files" / -1073552680 "Set-to-operationalfor unacknowledged UDID" (fix available for AR >= B4.92)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID:730255 / Support ID: 400356023
online project compare
Activation ofSafeDESIGNER option "Download project source to SL (online project compare)" didn't have any effect (requires mappSafety 5.15).
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 733990
data sheet V2.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 754040 / Support ID: 400374830
data sheet: SafeLOGIC parameter "Process data transfer rate = Low" leads toconnection abort to local SafeNODEs
In rare cases, if "Process data transfer rate = Low" is set, the connectionto SafeNODEs present in the network may be aborted. A corresponding note hasbeen added to the "Process data transfer rate" parameter.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(591), 11\61968_1.fw(591)

Version 2.4.1.1:

ID: 710995 / Support ID: 400324450
Data sheet: Improveddescription of max data width
Data sheet: Improved description of max data width
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 721455
data sheet V2.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 726670
The power calculation ofthe modules is supported
The data for the power calculation of the data sheet is included in the HWX.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(590)

Version 2.4.0.0:

ID: 593200
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 672165 / Support ID: 400308545
Technical data: "Communication with each other": Generalized statement regarding the CPU used
Technical data: "Communication witheach other": Generalized statement regarding the CPU used
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 672470 / Support ID: 400308552
Variable status issue
Having Variable status active for a long time could lead to SLX failsafe state with certain projects (logger entries 110337/114433 respectively -1073561855/-1073565951).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688905
data sheet V2.08
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 691590
Improvementof the internal voltage monitoring.
Improvement of the internal voltage monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 691600
Improvement of the feedback diagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 692355
Support of the DYNlink interface
The DYNlink interface is supported by the safe inputs.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 692400 / Support ID: 400311305
The OSDD signal at the pulse output is corrected.
The OSDD signal at the pulse output is output correctly even when not in use.
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:Yes

ID: 694305
Loss of safety connection
Loss of safety connection, even though the parametrized "safe data duration" is longer than thenetwork failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\61968_1.fw(590)

Version 2.2.0.0:

ID: 539430
Safe Commissioning Options
support additional data types
ATTENTION:
- requires AR E4.71 or A4.72 and mappSafety 5.8 or higher
- at least one Safe Commissioning Option with data type BOOL must be used also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channeldescription changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 647160
data sheet V2.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 668580
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671505
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(580)

Version 2.1.0.3:

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 2.1.0.0:

ID: 541670
major (even incompatible) changes for mapp Safety

First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!

Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 580780 / Support ID: 400244031
Setup Mode signaling
Setup Mode is now signaled with "S" and "E" LED.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628065
safety response time

The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This couldlead to an increased safety response time.

Channel descriptionchanged: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 1.10.10.3:

ID: 626175
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635320 / Support ID: 400280438, 400278830, 400284804
fix logger entry 123622
SLX didn't enter RUN state and loggernumber 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmwarechanged: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.1:

ID: 635320 / Support ID: 400280438, 400278830
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.0:

ID: 626175
safety response time
The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.9.0:

ID: 618250
logger entry 112174, 108078
Logger entry 112174, 108078 couldhappen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(330)

Version 1.10.5.0:

ID: 580755
logger message 106773
Fix for logger message 106773 "Parameter checksum sizes do not match".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(326)

Version 1.10.4.1:

ID: 595830
First official upgrade
First official upgrade
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(326)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
2.4.3.0 * 01/03/2023 5 Mo EXE AS4_HW_X20SLX806.exe
Description V4.6 HW Upgrade (X20SLX806)

Revision information X20SLX806

Version 2.4.3.0:

ID: 763720 / Support ID: 400394920
SafeDomain to SafeDomain communication with differing "Process data transfer rate" setting
SafeDomain to SafeDomain communication could not be established if "Processdata transfer rate" setting differed between Managing and Connected SafeDomain.
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes
Firmware: 10\61968_1.fw(592), 11\61968_1.fw(592)

Version 2.4.2.0:

ID: 673420 / Support ID: 400370828, 400378297
Safe Commissioning Options without SAFEBOOL
Logger message "external machine options discrepancy" was triggered by mistake when Safe Commissioning Options where used without using any channel SafeCommissioningOptionsBITxxx
(fix available for AR >= B4.92)
Channel description changed:No
Configuration description changed: No
Firmware changed: No

ID: 673735
"CLEAR DATA" Safe Commissioning Options
"CLEAR DATA" did not delete the data for Safe Commissioning Options with data types SAFEINT, SAFEDINT and SAFEDWORD (fix available for AR >= B4.92).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 725975
logger messages "Inconsistent UDID files"/ "Set-to-operational for unacknowledged UDID"
Fix -1073552872 "Inconsistent UDID files" / -1073552680 "Set-to-operationalfor unacknowledged UDID" (fix available for AR >= B4.92)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 730255 / Support ID: 400356023
online project compare
Activation of SafeDESIGNER option "Download project source to SL (online project compare)" didn't have any effect (requires mappSafety 5.15).
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 733990
data sheet V2.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 754040 / Support ID: 400374830
data sheet: SafeLOGIC parameter "Processdata transfer rate = Low" leads to connection abort to local SafeNODEs
In rare cases, if "Process data transfer rate = Low" is set, the connectionto SafeNODEs present in the network may be aborted. A corresponding note has beenadded to the "Process data transfer rate" parameter.
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No
Firmware: 10\61968_1.fw(591), 11\61968_1.fw(591)

Version 2.4.1.1:

ID: 710995 / Support ID: 400324450
Data sheet: Improved description of max data width
Data sheet: Improved description of max data width
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 721455
data sheet V2.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 726670
The power calculation of the modules is supported
The data for the power calculation of the data sheetis included in the HWX.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(590)

Version 2.4.0.0:

ID: 593200
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 672165 / Support ID: 400308545
Technical data: "Communication with each other": Generalized statement regarding the CPU used
Technical data: "Communication with eachother": Generalized statement regarding the CPU used
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No

ID: 672470 / Support ID: 400308552
Variable status issue
Having Variable status active for a long time could lead to SLX failsafe state with certain projects (logger entries 110337/114433 respectively -1073561855/-1073565951).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688905
data sheet V2.08
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 691590
Improvement of the internal voltage monitoring.
Improvement of the internal voltage monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 691600
Improvement of the feedback diagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration description changed:No
Firmware changed: Yes

ID: 692355
Support of the DYNlinkinterface
The DYNlink interface is supported by the safe inputs.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 692400 / Support ID: 400311305
The OSDD signal at the pulse output is corrected.
The OSDD signal at the pulse output is output correctly even when not in use.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694305
Loss of safety connection
Loss of safety connection, even though the parametrized "safe data duration" is longer than the network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\61968_1.fw(590)

Version 2.2.0.0:

ID: 539430
Safe Commissioning Options
support additional data types
ATTENTION:
- requires AR E4.71 or A4.72 and mappSafety 5.8 or higher
- at least one Safe Commissioning Option with data type BOOL must be used also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: Yes
Configuration description changed: Yes
Firmwarechanged: Yes

ID: 647160
data sheet V2.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 668580
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671505
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC andSafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(580)

Version 2.1.0.3:

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 2.1.0.0:

ID: 541670
major (even incompatible) changes for mapp Safety

First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!

Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 580780 / Support ID: 400244031
Setup Mode signaling
Setup Mode is now signaled with "S" and"E" LED.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628065
safety response time

The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safedata duration"/"additional tolerated packet loss".
This could leadto an increased safety response time.

Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 1.10.10.3:

ID: 626175
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635320 / Support ID: 400280438, 400278830, 400284804
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.1:

ID: 635320 / Support ID: 400280438, 400278830
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 637055
newAR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.0:

ID: 626175
safety response time
The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.9.0:

ID: 618250
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(330)

Version 1.10.5.0:

ID: 580755
logger message 106773
Fix for logger message 106773 "Parameter checksum sizes donot match".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(326)

Version 1.10.4.1:

ID: 595830
First official upgrade
First official upgrade
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(326)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
2.4.2.0 * 08/09/2022 5 Mo EXE AS4_HW_X20SLX806.exe
Description V4.6 HW Upgrade (X20SLX806)

Revision information X20SLX806

Version 2.4.2.0:

ID: 673420 / Support ID: 400370828, 400378297
Safe Commissioning Options without SAFEBOOL
Logger message "external machine options discrepancy" was triggered by mistake when Safe Commissioning Options where used without using any channel SafeCommissioningOptionsBITxxx
(fix available for AR >= B4.92)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 673735
"CLEAR DATA" Safe Commissioning Options
"CLEAR DATA" did not delete thedata for Safe Commissioning Options with data types SAFEINT, SAFEDINT and SAFEDWORD (fix available for AR >= B4.92).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 725975
logger messages "Inconsistent UDID files" / "Set-to-operational for unacknowledged UDID"
Fix -1073552872 "Inconsistent UDID files" /-1073552680 "Set-to-operational for unacknowledged UDID" (fix available for AR >= B4.92)
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 730255 / Support ID: 400356023
online project compare
Activation of SafeDESIGNER option "Download project source to SL (online project compare)" didn't have any effect (requires mappSafety 5.15).
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No

ID: 733990
data sheet V2.15
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 754040 / SupportID: 400374830
data sheet: SafeLOGIC parameter "Process data transfer rate = Low" leads toconnection abort to local SafeNODEs
In rare cases, if "Process data transfer rate = Low" is set, the connectionto SafeNODEs present in the network may be aborted. A corresponding note has been added to the "Process data transfer rate" parameter.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware:10\61968_1.fw(591), 11\61968_1.fw(591)

Version 2.4.1.1:

ID: 710995 / Support ID: 400324450
Data sheet: Improved description of max data width
Data sheet: Improved description of max data width
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 721455
data sheet V2.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 726670
The power calculation of the modules is supported
The data for the power calculation of the data sheet is included in the HWX.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(590)

Version 2.4.0.0:

ID: 593200
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 672165 / Support ID: 400308545
Technical data: "Communication with each other": Generalized statement regarding the CPU used
Technical data: "Communication with each other": Generalized statement regarding the CPU used
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 672470 / Support ID: 400308552
Variable status issue
Having Variable status active for a long time could lead to SLX failsafe state with certain projects (logger entries 110337/114433 respectively -1073561855/-1073565951).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688905
data sheet V2.08
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 691590
Improvement of the internal voltage monitoring.
Improvement of the internal voltage monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 691600
Improvement of the feedback diagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 692355
Support of the DYNlink interface
The DYNlink interface is supported by the safe inputs.
Channel description changed: No
Configuration description changed: Yes
Firmware changed:Yes

ID: 692400 / Support ID: 400311305
The OSDD signal at the pulse output is corrected.
The OSDD signal at the pulse output is output correctly even when not in use.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694305
Loss of safety connection
Loss of safety connection, even though the parametrized "safe data duration" is longer than the network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\61968_1.fw(590)

Version 2.2.0.0:

ID: 539430
Safe Commissioning Options
support additionaldata types
ATTENTION:
- requires AR E4.71 or A4.72 and mappSafety 5.8 or higher
- at least one Safe Commissioning Option with data type BOOL must be used also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 647160
data sheet V2.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID:668580
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671505
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(580)

Version 2.1.0.3:

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel descriptionchanged: No
Configuration description changed: No
Firmware changed:No
Firmware: 10\61968_1.fw(570)

Version 2.1.0.0:

ID: 541670
major (even incompatible) changes for mapp Safety

First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!

Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 580780 / Support ID: 400244031
SetupMode signaling
Setup Mode is now signaled with "S" and "E" LED.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628065
safety response time

The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.

Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 1.10.10.3:

ID: 626175
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635320 / Support ID: 400280438, 400278830, 400284804
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.1:

ID: 635320 / SupportID: 400280438, 400278830
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.0:

ID: 626175
safety response time
The check of the network transmission time of cyclicdata tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to anincreased safety response time.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.9.0:

ID: 618250
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(330)

Version 1.10.5.0:

ID: 580755
logger message 106773
Fix for logger message 106773 "Parameter checksum sizes do not match".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(326)

Version 1.10.4.1:

ID: 595830
First official upgrade
First official upgrade
Channel description changed: No
Configuration description changed:No
Firmware changed: No
Firmware: 1\61968_1.fw(326)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
2.4.1.1 * 18/08/2021 3 Mo EXE AS4_HW_X20SLX806.exe
Description V4.6 HW Upgrade (X20SLX806)

Revision information X20SLX806

Version 2.4.1.1:

ID: 710995 / Support ID: 400324450
Data sheet: Improved description of max data width
Data sheet: Improved description of max data width
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 721455
data sheet V2.10
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 726670
The power calculation of the modules is supported
The data for the power calculation of the data sheet is included in the HWX.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(590)

Version 2.4.0.0:

ID: 593200
SafeDOMAIN-to-SafeDOMAIN communication: Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13,X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 672165 / Support ID: 400308545
Technical data: "Communication with each other": Generalized statement regarding the CPU used
Technical data: "Communication with each other": Generalized statement regarding the CPU used
Channel description changed: No
Configuration description changed: No
Firmwarechanged: No

ID: 672470 / Support ID: 400308552
Variable status issue
Having Variable status active for a long time could lead to SLX failsafe state with certain projects (logger entries 110337/114433 respectively -1073561855/-1073565951).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688905
data sheet V2.08
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 691590
Improvement of the internal voltage monitoring.
Improvement of the internal voltage monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 691600
Improvement of the feedback diagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration descriptionchanged: No
Firmware changed: Yes

ID: 692355
Support of the DYNlink interface
The DYNlink interface is supported by the safe inputs.
Channel description changed: No
Configuration description changed:Yes
Firmware changed: Yes

ID: 692400 / Support ID: 400311305
The OSDD signal at the pulse output is corrected.
The OSDD signal at the pulse output is output correctly even when not in use.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694305
Loss of safety connection
Loss of safety connection, even though the parametrized "safe data duration" is longer thanthe network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\61968_1.fw(590)

Version 2.2.0.0:

ID: 539430
Safe Commissioning Options
support additional data types
ATTENTION:
- requires AR E4.71 or A4.72 and mappSafety 5.8 or higher
- at least one Safe Commissioning Option with data type BOOL must be used also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 647160
data sheet V2.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 668580
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671505
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(580)

Version 2.1.0.3:

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 2.1.0.0:

ID: 541670
major (even incompatible) changes for mappSafety

First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety"in help!

Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 580780 / Support ID: 400244031
Setup Mode signaling
Setup Mode is now signaled with "S" and "E" LED.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628065
safety response time

The check of the network transmission time ofcyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.

Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 1.10.10.3:

ID: 626175
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635320 / Support ID: 400280438, 400278830,400284804
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.1:

ID: 635320 / Support ID: 400280438, 400278830
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.0:

ID: 626175
safety response time
The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.9.0:

ID: 618250
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(330)

Version 1.10.5.0:

ID: 580755
logger message 106773
Fix for logger message 106773 "Parameter checksumsizes do not match".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(326)

Version 1.10.4.1:

ID: 595830
First official upgrade
First official upgrade
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(326)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
2.4.0.0 * 01/12/2020 3 Mo EXE AS4_HW_X20SLX806.exe
Description V4.6 HW Upgrade (X20SLX806)

Revision information X20cSLX402

Version 2.4.0.0:

ID: 593200
SafeDOMAIN-to-SafeDOMAIN communication:Connected SafeDOMAIN
Provide a Connected SafeDOMAIN (required minimum versions: Automation Runtime A4.90, mappSafety 5.13, X20(c)SL81xx V2.3.0.0)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 672165 / Support ID: 400308545
Technical data: "Communication with each other": Generalized statement regardingthe CPU used
Technical data: "Communication with each other": Generalized statement regarding the CPU used
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 672470 / Support ID: 400308552
Variable status issue
Having Variable status active for a long time could lead to SLX failsafe state with certain projects (logger entries 110337/114433 respectively -1073561855/-1073565951).
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688905
data sheet V2.08
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 691590
Improvement of the internal voltagemonitoring.
Improvement of the internal voltage monitoring.
Channeldescription changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 691600
Improvement of the feedback diagnosis.
Improvement of the feedback diagnosis of the output.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 692355
Support of the DYNlink interface
TheDYNlink interface is supported by the safe inputs.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 692400 / Support ID: 400311305
The OSDD signal at the pulse output is corrected.
The OSDD signal at the pulse output is output correctly even when not in use.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 694305
Loss of safety connection
Loss of safety connection, even though the parametrized "safe data duration" is longer than the network failure
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 10\61968_1.fw(590)

Version 2.2.0.0:

ID: 539430
Safe Commissioning Options
support additional data types
ATTENTION:
- requires AR E4.71 or A4.72 and mappSafety 5.8 or higher
- at least one Safe Commissioning Option with data type BOOL mustbe used also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 647160
data sheet V2.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 668580
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671505
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(580)

Version 2.1.0.3:

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 2.1.0.0:

ID: 541670
major (even incompatible) changes for mapp Safety

First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!

Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 580780 / Support ID: 400244031
Setup Mode signaling
Setup Mode is now signaled with "S" and "E" LED.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628065
safety response time

The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.

Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 1.10.10.3:

ID: 626175
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed:No
Configuration description changed: No
Firmware changed: No

ID: 635320 / Support ID: 400280438, 400278830, 400284804
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.1:

ID: 635320 / Support ID: 400280438, 400278830
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.0:

ID: 626175
safety response time
The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.9.0:

ID: 618250
logger entry112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(330)

Version 1.10.5.0:

ID: 580755
logger message 106773
Fix for logger message 106773 "Parameter checksum sizes do not match".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(326)

Version 1.10.4.1:

ID: 595830
First official upgrade
First official upgrade
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(326)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
2.2.0.0 * 05/03/2020 3 Mo EXE AS4_HW_X20SLX806.exe
Description V4.6 HW Upgrade (X20SLX806)

Revision information X20cSLX402

Version 2.2.0.0:

ID: 539430
Safe Commissioning Options
supportadditional data types
ATTENTION:
- requires AR E4.71 or A4.72 and mappSafety 5.8 or higher
- at least one Safe Commissioning Option with data type BOOL must be used also
- use SafeKEY FORMAT to remove Safe Commissioning Options with data types other than BOOL from target
Channel descriptionchanged: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 647160
data sheet V2.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 668580
Adaptations for Automation Studio 4.8
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 671505
SafeDOMAIN-to-SafeDOMAIN communication
Support SafeDOMAIN-to-SafeDOMAIN communication between SafeLOGIC and SafeLOGIC-X (requires mappSafety 5.10 or higher)
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(580)

Version 2.1.0.3:

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 2.1.0.0:

ID: 541670
major (even incompatible) changes for mapp Safety

First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!

Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 580780 / Support ID: 400244031
Setup Mode signaling
Setup Mode is now signaled with "S" and "E" LED.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628065
safety response time

The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.

Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 1.10.10.3:

ID: 626175
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635320 / Support ID: 400280438, 400278830, 400284804
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.1:

ID: 635320 / Support ID: 400280438, 400278830
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.0:

ID: 626175
safety response time
The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This couldlead to an increased safety response time.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.9.0:

ID: 618250
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(330)

Version 1.10.5.0:

ID: 580755
logger message106773
Fix for logger message 106773 "Parameter checksum sizes do not match".
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(326)

Version 1.10.4.1:

ID: 595830
First official upgrade
First official upgrade
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(326)
Version Langue
Système d'exploitation
Date
Taille
Type Téléchargement
2.1.0.3 * 05/07/2019 3 Mo EXE AS4_HW_X20SLX806.exe
Description V4.6 HW Upgrade (X20SLX806)

Revision information X20cSLX402

Version 2.1.0.3:

ID: 637055
new AR targets
support new AR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 2.1.0.0:

ID: 541670
major (even incompatible) changes for mapp Safety
First upgrade for mapp Safety.
ATTENTION: existing applications must be adapted - see chapter "Switching to mapp Safety" in help!
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 580780 / Support ID: 400244031
Setup Mode signaling
Setup Mode is now signaled with "S" and "E" LED.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 628065
safety response time
The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increased safety response time.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 10\61968_1.fw(570)

Version 1.10.10.3:

ID: 626175
data sheet V1.141
See chapture "Version history" in the data sheet.
i.a. calculation of Safety response time has been updated.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 635320 / Support ID: 400280438, 400278830, 400284804
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.1:

ID: 635320 / Support ID: 400280438, 400278830
fix logger entry 123622
SLX didn't enter RUN state and logger number 123622 was entered when using 10 other safety modules.
Channel description changed: No
Configuration description changed: No
Firmware changed: No

ID: 637055
new AR targets
support newAR targets X20CPx68x and xPC22xx
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.10.0:

ID: 626175
safety response time
The check of the network transmission time of cyclic data tolerated values up to 12ms higher than configured by the parameters "safe data duration"/"additional tolerated packet loss".
This could lead to an increasedsafety response time.
Channel description changed: No
Configurationdescription changed: Yes
Firmware changed: No
Firmware: 1\61968_1.fw(330)

Version 1.10.9.0:

ID: 618250
logger entry 112174, 108078
Logger entry 112174, 108078 could happen sporadically with large projects.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\61968_1.fw(330)

Version 1.10.5.0:

ID: 580755
logger message 106773
Fix for logger message 106773 "Parameter checksum sizes do not match".
Channel description changed: No
Configuration description changed: No
Firmwarechanged: Yes
Firmware: 1\61968_1.fw(326)

Version 1.10.4.1:

ID: 595830
First official upgrade
First official upgrade
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\61968_1.fw(326)