Short description
I/O module | 4 safe type A digital inputs, 4 pulse outputs, 24 VDC, 2 safe type B2 digital outputs, 24 VDC, 0.2 A, OSSD <10 µs, reACTION Technology |
General information
Safety characteristics
I/O power supply
Nominal voltage | 24 VDC |
Voltage range | 24 VDC -15% / +20% |
Integrated protection | Reverse polarity protection |
Safe digital inputs
Safe digital HS-HS outputs
Quantity | 2 |
Variant | FET, 2x positive switching, type B2, output level readable |
Nominal voltage | 24 VDC |
Nominal output current | 0.2 A |
Total nominal current | 0.4 A |
Output protection | See section "Inrush current behavior for output channels". |
Braking voltage when switching off inductive loads | Max. 45 VDC |
Error detection time | 1 s |
Insulation voltage between channel and bus | 500 Veff |
Peak short-circuit current | See section "Inrush current behavior for output channels". |
Leakage current when the output is switched off | <100 µA |
RDS(on) | 5 Ω |
Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
Max. switching frequency | See section "Inrush current behavior for output channels". |
Test pulse length | Max. 10 µs |
Max. capacitive load | 100 nF |
Current on loss of ground
IOUT | <100 µA |
IGND | <200 mA |
Pulse outputs
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | 0 to 2000 m, no limitation |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | 0 to 60°C |
Vertical mounting orientation | 0 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 2x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately. |
Pitch | 25+0.2 mm |
Référence produit:
X20SRT402Description:
- reACTION Technology module
- 4 high-speed safe digital inputs, sink circuit
- 4 pulse outputs
- Software input filter configurable for each channel
- 2 high-speed safe digital outputs, output type B with 0.2 A, source circuit
- Safe reACTION task cycle times starting at 150 µs
- Integrated output protection
This reACTION Technology module is equipped with 4 high-speed safe digital inputs and 2 high-speed safe digital outputs. It is designed for a nominal voltage of 24 VDC.
The module can be used to read in digital signals and to control actuators in safety-related applications up to PL e or SIL 3.
Ultrafast reACTION Technology makes it possible to control internal I/O channels with cycle times down to 150 µs. All commands that can be used for reACTION programs are available as function blocks in special libraries (e.g. AsIORTI). Programming in compliance with IEC 61131-3 requirements takes place in the Function Block Diagram editor in Automation Studio.
The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.
The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of switching cycles. The "high-side high-side" variant (output type B) is required for actuators with reference potential (e.g. enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. The safe digital output modules are equipped with an error interlock in the event of network errors.
This module is designed for X20 12-pin terminal blocks.
Accessoires obligatoires
Automation Studio HW Upgrades | Version (date) | Téléchargement |
---|---|---|
V4.2 HW Upgrade (X20SRT402) | EXE / 4 Mo | |
V4.6 HW Upgrade (X20SRT402) | EXE / 3 Mo | |
V6.0 HW Upgrade (X20SRT402) | EXE / 3 Mo |
Certifications | Version (date) | Téléchargement |
---|---|---|
E115267 UL CoC X20 | PDF / 1 Mo | |
EU Declaration FS PLC X20 | PDF / 210 Ko | |
FS Certificate SafeDESIGNER, SafeLOGIC, SafeIO | PDF / 1 Mo | |
FS Certificate mapp Safety | PDF / 1 Mo | |
FTZU 09 ATEX 0083X | PDF / 771 Ko | |
UK Declaration FS PLC X20 | PDF / 112 Ko |
Documentation | Version (date) | Téléchargement |
---|---|---|
Data sheet X20SRTxxx - Legacy | PDF / 4 Mo | |
Data sheet X20SRTxxx - mapp Safety | PDF / 2 Mo | |
Installation- / EMC-Guide | PDF / 20 Mo | |
X20 Package leaflet ATEX/CSA | PDF / 2 Mo | |
X20 System User´s Manual | PDF / 7 Mo |
E-CAD (modèles Electro ou EPLAN) | Version (date) | Téléchargement |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 Mo |
Outils / Utilitaires / Exemples | Version (date) | Téléchargement |
---|---|---|
Sistema library | ZIP / 336 Ko |