Short description
Communication module 1x PROFIBUS DP V0/V1 slave
General information
B&R ID code 0xA717
Status indicators Module status, data transfer
Diagnostics
Module status Yes, using LED status indicator and software
Network status Yes, using LED status indicator and software
Data transfer Yes, using LED status indicator
Power consumption 1.8 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
CCS Yes
LR ENV1
KR Yes
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
KC Yes
Interfaces
Interface IF1
Fieldbus PROFIBUS DP V0/V1 slave
Variant 9-pin female DSUB connector
Max. distance 1200 m
Transfer rate Max. 12 Mbit/s
Controller netX100
Cyclic data
Input data Max. 244 bytes
Output data Max. 244 bytes
Electrical properties
Electrical isolation PLC isolated from PROFIBUS (IF1)
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Slot In the X20 PLC and expandable bus controller X20BC1083
Número de material:
X20IF1063-1
Descripción:
  • PROFIBUS DP V1 slave

The interface module is equipped with a PROFIBUS DP V1 interface. This allows the B&R system (I/O modules, POWERLINK, etc.) to be connected to systems from other manufacturers and makes it possible to quickly and easily transfer data in both directions.

The interface module can be operated in X20 CPUs or in the expandable POWERLINK bus controller X20BC1083.

Accesorios opcionales
Infrastructure components
0G1000.00-090 Bus connector, RS485, for PROFIBUS networks
Actualizaciones de hardware de Automation Studio Versión (fecha) Descargar
V3.0 HW Upgrade (X20IF1063-1) EXE / 1 MB
V4.0 HW Upgrade (X20IF1063-1) EXE / 5 MB
Archivos de descripción de equipos de bus de campo Versión (fecha) Descargar
X20IF1063-1 GSD Package ZIP / 4 KB
Certificados Versión (fecha) Descargar
244665 CSA HazLoc CoC X20, X67 PDF / 158 KB
ABS Certificate of Product Design Assessment - X20 IO Series PDF / 2 MB
BV Type Approval Certificate - X20 PDF / 556 KB
CCS Type Approval Certificate - X20 PDF / 285 KB
Compass Safe Distance Certificate - X20 PDF / 1 MB
DNV Type Approval Certificate - X20 PDF / 194 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
FTZU 09 ATEX 0083X PDF / 771 KB
KR Type Approval Certificate MIL39390-AC003 (X20 System) PDF / 758 KB
Lloyds Register PDF / 502 KB
PROFIBUS DP Certificate PDF / 150 KB
RINA Type Approval Certificate - X20 / Power Panel T30 PDF / 1 MB
X20, X67 KC certificates PDF / 6 MB
Documentación Versión (fecha) Descargar
Data sheet X20(c)IF1063-1 PDF / 2 MB
Installation- / EMC-Guide PDF / 20 MB
X20 Package leaflet ATEX/CSA PDF / 2 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (plantillas Electro o EPLAN) Versión (fecha) Descargar
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (plantillas mecánicas) Versión (fecha) Descargar
3D File DXF/STEP X20 Interface module X20(c)IF106x(-1) ZIP / 1 MB

Seleccione país e idioma

B&R Logo