Short description
Communication module | DeviceNet scanner (master) |
General information
B&R ID code | 0xA70C |
Status indicators | Module status, network status, data transfer, terminating resistor |
Diagnostics | |
Module status | Yes, using LED status indicator and software |
Network status | Yes, using LED status indicator and software |
Data transfer | Yes, using LED status indicator |
Terminating resistor | Yes, using LED status indicator |
Power consumption | 1.1 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
CCS | Yes |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
KC | Yes |
Interfaces
Interface IF1 | |
Fieldbus | DeviceNet scanner (master) |
Variant | 5-pin male multipoint connector |
Max. distance | 500 m |
Transfer rate | Max. 500 kbit/s |
Terminating resistor | Integrated in module |
Controller | netX100 |
Memory | 8 MB SDRAM |
Electrical properties
Electrical isolation | PLC isolated from DeviceNet (IF1) |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order 1x terminal block TB2105 separately. |
Slot | In the X20 PLC and expandable bus controller X20BC1083 |
Número de material:
X20IF1051-1Descripción:
- DeviceNet scanner
- Integrated terminating resistor
The interface module is equipped with a DeviceNet scanner interface. This allows third-party components to be integrated in the B&R system and makes it possible to quickly and easily transfer data in both directions.
The interface module can be operated in the X20 controllers or in the expandable X20BC1083 POWERLINK bus controller.
Accesorios obligatorios
Terminal blocks
0TB2105.9010 | Accessory terminal block, 5-pin, screw clamp terminal block 2.5 mm² |
0TB2105.9110 | Accessory terminal block, 5-pin, push-in terminal block 2.5 mm² |
Actualizaciones de hardware de Automation Studio | Versión (fecha) | Descargar |
---|---|---|
V3.0 HW Upgrade (X20IF1051-1) | EXE / 657 KB | |
V3.0 HW Upgrade (X20IF1051-1) | EXE / 1 MB | |
V4.0 HW Upgrade (X20IF1051-1) | EXE / 3 MB |
Documentación | Versión (fecha) | Descargar |
---|---|---|
Data sheet X20IF1051-1 | PDF / 2 MB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
X20 System User´s Manual | PDF / 7 MB |
E-CAD (plantillas Electro o EPLAN) | Versión (fecha) | Descargar |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD (plantillas mecánicas) | Versión (fecha) | Descargar |
---|---|---|
3D File DXF/STEP X20 Interface module CAN/DeviceNet | ZIP / 946 KB | |
Dimensions PDF X20 Interface Module CAN/DeviceNet | PDF / 4 KB |