Short description
System module | Power supply of 4 potentiometers with ±10 V |
General information
B&R ID code | 0x1F43 |
Status indicators | Potentiometer power supply monitoring per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Open circuit | Yes, using LED status indicator and software |
Overload | Yes, using LED status indicator and software |
Power consumption | |
Bus | 0.01 W |
Internal I/O | 1.8 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV |
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
CCS | Yes |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV |
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
KC | Yes |
Potentiometer power supply
Number of power supplies | 4 |
Voltage | ±10 V |
Potentiometer resistance | 1 kΩ to 10 kΩ |
Load | Max. 20 mA per power supply channel |
Short-circuit proof | Yes |
Basic accuracy | |
+10 V | ±0.12% at 25°C |
-10 V | ±0.21% at 25°C |
20 V | ±0.165% at 25°C |
Insulation voltage between channel and bus | 500 Veff |
Max. drift | |
+10 V | ±0.00012 %/°C |
-10 V | ±0.00032 %/°C |
20 V | ±0.00022 %/°C |
Electrical properties
Electrical isolation |
Channel isolated from bus Channel not isolated from channel
|
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2 mm |
Material number:
X20PS4951Description:
- Open circuit and short circuit detection
- Simple implementation of potentiometer inputs
- 4x supply
In order to connect potentiometers, modules must first be supplied with the appropriate voltage. The potentiometer supply module can be used to supply four potentiometers with ±10 V. The data is evaluated using standard analog input modules.
Mandatory Accessories
Automation Studio HW Upgrades | Version (Date) | Download |
---|---|---|
V2.6 HW Upgrade (X20PS4951) | EXE / 914 KB | |
V3.0 HW Upgrade (X20PS4951) | EXE / 1 MB | |
V4.0 HW Upgrade (X20PS4951) | EXE / 620 KB |
Documentation | Version (Date) | Download |
---|---|---|
Data sheet X20PS4951 | PDF / 195 KB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X20 Package leaflet ATEX/CSA | PDF / 2 MB | |
X20 System User´s Manual | PDF / 7 MB |
E-CAD (Electro or EPLAN Templates) | Version (Date) | Download |
---|---|---|
X20 EPLAN P8 from V2.4 | EXE / 160 MB |
M-CAD (Mechan. Templates) | Version (Date) | Download |
---|---|---|
3D File DXF/STEP X20 Electronic module | ZIP / 10 KB | |
3D File STEP X20 I/O-Slice | ZIP / 872 KB | |
Dimensions PDF X20 Electronic module | PDF / 3 KB |