Short description
I/O module | 4 digital inputs, 2 digital outputs, 1 input for full-bridge strain gauge |
General information
B&R ID code | 0x1CDF |
Status indicators | I/O function per channel, supply voltage, bus function |
Diagnostics | |
Outputs | Yes, using LED status indicator |
I/O power supply | Yes, using LED status indicator and software |
Connection type | |
X2X Link | M12, B-coded |
Inputs/Outputs | 4x M12, A-coded |
I/O power supply | M8, 4-pin |
Power consumption | |
Internal I/O | 1 W |
X2X Link power supply | 0.75 W |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX |
Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X |
UL |
cULus E115267 Industrial control equipment |
HazLoc |
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
KC | Yes |
I/O power supply
Strain gauge supply
Voltage | 4.422 VDC / max. 60 mA |
Voltage drop for short-circuit protection at 60 mA | Max. 0.36 VDC |
Short-circuit proof | Yes |
Sensor/Actuator power supply
Voltage | I/O power supply minus voltage drop for short-circuit protection |
Voltage drop for short-circuit protection at 0.5 A | Max. 2 VDC |
Summation current | Max. 0.5 A |
Short-circuit proof | Yes |
Full-bridge strain gauge
Strain gauge factor | ±15.625 to ±125 mV/V, configurable using software |
Input type | Differential, used to evaluate a full-bridge strain gauge |
Digital converter resolution | 24-bit |
Conversion time | Depends on the configured data output rate |
Data output rate | 10 to 3750 samples per second, configurable using software |
Input filter | |
Cutoff frequency | 50 kHz |
Order | 1 |
Slope | 20 dB |
Operating range / Measurement sensor | 75 to 5000 Ω |
Influence of cable length | Twisted and shielded conductors, cable length as short as possible, cable routing separate from load circuits, without intermediate terminal to sensor |
Input protection | RC protection |
Input current | 450 nA |
Common-mode range |
0 to 3 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on the inputs "Input +" and "Input -" |
Insulation voltage between input and bus | 500 Veff |
Gain | 1 to 8, configurable using software |
Conversion procedure | Sigma-delta |
Output of digital value | |
Broken bridge supply line | Value approaching 0 |
Broken sensor line | Value approaching ±final value |
Valid range of values | 0x7FFF FFFF to 0x8000 0001 |
Strain gauge supply | |
Voltage | 4.5 VDC / max. 60 mA |
Connection | 4-wire connections |
Short-circuit and overload-proof | Yes |
Quantization | |
LSB value (16-bit) | |
69 mV/V | 9.31 µV |
138 mV/V | 18.6 µV |
276 mV/V | 37.3 µV |
553 mV/V | 74.6 µV |
LSB value (24-bit) | |
69 mV/V | 36.4 nV |
138 mV/V | 72.8 nV |
276 mV/V | 146.0 nV |
553 mV/V | 251.0 nV |
Temperature coefficient | 50 ppm/°C |
Digital inputs
Quantity | 4 |
Nominal voltage | 24 VDC |
Input characteristics per EN 61131-2 | Type 1 |
Input voltage | 24 VDC ±25% |
Input current at 24 VDC | Typ. 5 mA |
Input circuit | Sink |
Input filter | |
Hardware | <1 ms |
Software | - |
Input resistance | Typ. 4.27 kΩ |
Sensor power supply | 0.5 A summation current |
Switching threshold | |
Low | <5 VDC |
High | >15 VDC |
Insulation voltage between channel and bus | 500 Veff |
Digital outputs
Quantity | 2 |
Nominal voltage | 24 VDC |
Switching voltage | 24 VDC ±25% |
Output circuit | Source |
Output protection | Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply |
Actuator power supply | External |
Insulation voltage between output and bus | 500 Veff |
Nominal output current | |
Output 1 | 0.5 A |
Output 2 | 1 A |
Switch-on time of output driver | |
Output 1 | |
Typical | 50 µs |
0 → 1 (90% VOut) | Max. 100 µs |
Output 2 | |
Typical | 60 µs |
0 → 1 (90% VOut) | Max. 160 µs |
Switch-off time of output driver | |
Output 1 | |
Typical | 75 µs |
1 → 0 (90% VOut) | Max. 150 µs |
Output 2 | |
Typical | 15 µs |
1 → 0 (90% VOut) | Max. 50 µs |
Braking voltage when switching off inductive loads | |
Output 1 | -47 VDC |
Output 2 | Approx. 1 VDC |
Max. frequency | |
Output 1 | 100 Hz |
Output 2 | 1 kHz |
Electrical properties
Electrical isolation |
Channel isolated from bus and digital isolated from analog Digital not isolated from I/O power supply
|
Operating conditions
Mounting orientation | |
Any | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP67 |
Ambient conditions
Temperature | |
Operation | -25 to 60°C |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Mechanical properties
Dimensions | |
Width | 53 mm |
Height | 85 mm |
Depth | 42 mm |
Weight | 200 g |
Torque for connections | |
M8 | Max. 0.4 Nm |
M12 | Max. 0.6 Nm |
Materialenummer:
X67UM1352Beskrivelse:
- 1 strain gauge input with 24-bit resolution
- High data output rate (10 to 3,750 Hz)
- Adjustable gain
- 1 high-side output 24 VDC, 0.5 A
- 1 high-side output 24 VDC, 1.0 A
This module enables the remote connection of a force gauge using a strain gauge with a converter resolution of up to 24-bit. The data rate can be set from 0.26 ms to 100 ms. This module concept requires compensation in the measurement system. This compensation eliminates the absolute uncertainty in the measurement circuit, such as component tolerances, effective bridge voltage or zero point offset. The measurement precision refers to the absolute (compensated) value, which will only change as a result of changes in the operating temperature. The module is also equipped with 4 digital inputs and 2 digital outputs.
Automation Studio HW opgraderinger | Version (dato) | Download |
---|---|---|
V2.6 HW Upgrade (X67UM1352) | EXE / 1 MB | |
V3.0 HW Upgrade (X67UM1352) | EXE / 2 MB | |
V4.0 HW Upgrade (X67UM1352) | EXE / 1 MB |
Dokumentation | Version (dato) | Download |
---|---|---|
Datasheet X67UM1352 | PDF / 517 KB | |
Installation- / EMC-Guide | PDF / 20 MB | |
X67 System User´s Manual | PDF / 6 MB |
E-CAD (Elektro eller EPLAN skabeloner) | Version (dato) | Download |
---|---|---|
X67 EPLAN P8 from V2.4 | EXE / 105 MB |
M-CAD (Mechan. skabeloner) | Version (dato) | Download |
---|---|---|
3D File DXF/STEP X67 | ZIP / 4 MB |