Short description
Communication module EtherCAT master
General information
B&R ID code 0x2E3E
Status indicators Module status, network status, data transfer
Diagnostics
Module status Yes, using LED status indicator and software
Network status Yes, using LED status indicator and software
Data transfer Yes, using LED status indicator
Power consumption 2 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
Interfaces
Fieldbus EtherCAT (master)
Variant 2x shielded RJ45
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Controller netX100
Memory 8 MB SDRAM
Electrical properties
Electrical isolation PLC isolated from EtherCAT (IF1 and IF2)
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Slot In the X20 PLC and expandable bus controller X20BC1083
Materialenummer:
X20IF10G1-1
Beskrivelse:
  • EtherCAT master
  • Integrated switch for efficient cabling

The interface module is equipped with an EtherCAT master interface. This allows the B&R system (I/O modules, POWERLINK, etc.) to be connected to systems from other manufacturers and makes it possible to quickly and easily transfer data in both directions.

The interface module can be operated in the X20 controllers or in the expandable X20BC1083 POWERLINK bus controller.

The interface is equipped with 2 RJ45 connections. Both connections result in an integrated switch. This makes it easy to implement daisy chain cabling.

Automation Studio HW opgraderinger Version (dato) Download
V4.0 HW Upgrade (X20IF10G1-1) EXE / 3 MB
Dokumentation Version (dato) Download
Data sheet X20IF10G1-1 PDF / 2 MB
E-CAD (Elektro eller EPLAN skabeloner) Version (dato) Download
Makro-/Artikeldaten 4.0.4 (X20IF10G1-1) EXE / 487 KB
M-CAD (Mechan. skabeloner) Version (dato) Download
3D File STEP/DXF X20 Module ZIP / 1 MB

Vælg venligst land og sprog

B&R Logo