Short description
I/O module Measurement of ambient conditions:
Internal module temperature, relative humidity, operating hours, power-on cycles
General information
B&R ID code 0xF1AD
Status indicators Memory access, operating state, module status
Diagnostics
Module run/error Yes, using LED status indicator and software
Blackout mode
Scope Module
Function Module functionality
Standalone mode No
Power consumption
Bus 0.4 W
Internal I/O -
Additional power dissipation caused by actuators (resistive) [W] -
Technology Guard
Data retention 10 years at room temperature
Guaranteed erase/write cycles Up to 10 million
Application memory 241 bytes customized data
Coding 128-bit AES, SHA-256, 2048-bit RSA, 224-bit ECC
Certifications
CE Yes
UKCA Yes
UL cULus E115267
Industrial control equipment
DNV Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
CCS Yes
LR ENV1
ABS Yes
BV EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck
Temperature and humidity sensor
Sensor position Module-internal
Sampling rate 1 s
Temperature measurement
Measurement range -25 to 125°C
Resolution 0.1°C/LSB
Max. error ±0.3°C
Humidity measurement
Measurement range 5 to 95%
Resolution 1%/LSB
Max. error ±2% at 10 to 80% relative humidity
±3% at <10 and >80% relative humidity
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately.
Pitch 12.5+0.2 mm
Materialenummer:
X20CMR100
Beskrivelse:
  • Measurement and evaluation of the ambient conditions in the control cabinet
  • Recording ambient conditions
  • Recording operating hours and power-on cycles
  • Technology Guarding directly on the module
  • Supports blackout mode

The module is designed for measuring ambient conditions in the control cabinet as well as recording operating hours and power-on cycles. In addition, the module is equipped with a Technology Guard and supports blackout mode.

Measuring and evaluating ambient conditions

The ambient conditions are continuously evaluated by the module. The duration in which individual parameters are within certain ranges is stored internally. This makes it possible, for example, to determine how long the system remained in a certain temperature range. The histograms recorded by the module can be read out by the user.

Technology Guarding

With the integrated Technology Guard, it is possible to implement license protection directly via the module instead of the USB dongle. The same functions can be used as with the USB dongle.

Blackout mode

The integrated blackout mode ensures that module functionality is maintained even in the event of network failure.

Obligatorisk tilbehør
Bus modules
X20BM11 X20 bus module, 24 VDC keyed, internal I/O power supply connected through
X20BM15 X20 bus module, with node number switch, 24 VDC keyed, internal I/O power supply connected through
Terminal blocks
X20TB12 X20 terminal block, 12-pin, 24 VDC keyed
Automation Studio HW opgraderinger Version (dato) Download
V4.0 HW Upgrade (X20CMR100) EXE / 938 KB
V4.4 HW Upgrade (X20CMR100) EXE / 2 MB
Certifikater Version (dato) Download
BV Type Approval Certificate - X20 PDF / 556 KB
CCS Type Approval Certificate - X20 PDF / 285 KB
DNV Type Approval Certificate - X20 PDF / 194 KB
E115267 UL CoC X20 PDF / 1 MB
EU Declaration ATEX X20 PDF / 218 KB
EU Declaration of conformity PLC X20 PDF / 169 KB
Lloyds Register PDF / 502 KB
UK Declaration PLC X20 PDF / 151 KB
Dokumentation Version (dato) Download
Data sheet X20CMR100 PDF / 633 KB
Installation- / EMC-Guide PDF / 20 MB
X20 System User´s Manual PDF / 7 MB
E-CAD (Elektro eller EPLAN skabeloner) Version (dato) Download
X20 EPLAN P8 from V2.4 EXE / 160 MB
M-CAD (Mechan. skabeloner) Version (dato) Download
3D File DXF/STEP X20 Electronic module ZIP / 10 KB
3D File STEP X20 I/O-Slice ZIP / 872 KB
Dimensions PDF X20 Electronic module PDF / 3 KB

Vælg venligst land og sprog

B&R Logo