Short description
I/O module X90 mobile 4-channel analog input module for vibration measurement and analysis of condition monitoring tasks
General information
Nominal voltage 9 to 32 VDC
B&R ID code 0xEF81
Power consumption 1.59 W
Electrical isolation
Channel - Channel No
Channel - I/O power supply No
Certifications
UN ECE-R10 Yes
CE Yes
UKCA Yes
Analog inputs
Quantity 4
Input type IEPE sensor: Acceleration
Accuracy (analog input signal) at 25°C
Offset (based on 20 V measurement range) ±0.2%
Gain with sinusoidal signal where f = 100 Hz ±1%
Temperature drift (analog input signal)
Max. offset drift (based on 20 V measurement range) ±0.005 %/°C
Max. gain drift with sinusoidal signal where f = 100 Hz ±0.020 %/°C
Accuracy of frequency response (1 Hz to 10 kHz) ±5%
Digital converter resolution 24-bit
Short-circuit proof Yes
Open-circuit detection
Per channel Yes
Threshold voltage, typical Starting at 21.3 V (or greater) for more than 1 ms
Input voltage range
Common-mode voltage (UCM) -1 to 17 V
Differential voltage (UD) UCM ≤ 7 V: ±10 V
UCM > 7 V: ±(17 V - UCM)
Conversion procedure Sigma-delta
Crosstalk between channels ≤-70 dB
Type Vibration input
Sampling frequency 51.5625 kHz
Input high pass cutoff frequency 36 mHz
Input low pass cutoff frequency 20 kHz
Downsampling 200 Hz, 500 Hz, 1 kHz, 2 kHz, 5 kHz, 10 kHz (configurable)
Frequency resolution of spectra 0.0629 Hz, 0.1574 Hz, 0.3147 Hz, 0.6294 Hz, 1.5736 Hz, 3.1471 Hz
Sensor power supply IEPE, 5 mA constant current source (4.9 - 5.5 mA), can be switched off for each channel
Operating conditions
Mounting orientation
Any Yes
Degree of protection per EN 60529 IP69K
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -40 to 85°C housing surface
Vertical mounting orientation -40 to 85°C housing surface
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 100%, condensing
Storage 5 to 100%, condensing
Transport 5 to 100%, condensing
Mechanical properties
Dimensions
Width 47 mm
Length 95 mm
Materiálové číslo:
X90CM480.04-00
Popis:
  • 4-channel vibration measurement and analysis module
  • 24-bit resolution at 51.562 kHz
  • IEPE power supply
  • Extensive characteristic value calculation in the module
  • Data buffer upload

Option board X90CM480.04-00 provides a compact system for measuring and analyzing vibrations for use in applications such as condition monitoring for machinery and equipment.

The measurement unit consists of 4 vibration inputs with 24-bit converter resolution and a sampling frequency of 51.562 kHz. Each of the inputs has a separately switchable constant current source for supplying power to the IEPE sensors.

The option board integrates numerous algorithms for signal processing. These include configurable high and low pass filters, envelope generation and Fourier transformation.

Various parameters and configurable frequency bands are available to ensure seamless signal evaluation. The module performs calculations internally to minimize the load on the bus and CPU.

Whether used for traditional condition monitoring or as a means of process optimization, the maximum evaluable frequency of 10 kHz and maximum frequency resolution of under 63 mHz make the option board suitable for almost any application. If desired, the option board can also be used as a standard input module.

The ability to upload all values in the time and frequency domain also allows measurements to be evaluated externally or archived.

Volitelné příslušenství
Sensor cable
0ACC0020.01-1 Cable for accelerometer, length 2 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed
0ACC0050.01-1 Cable for accelerometer, length 5 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed
0ACC0100.01-1 Cable for accelerometer, length 10 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed
0ACC0150.01-1 Cable for accelerometer, length 15 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed
0ACC0200.01-1 Cable for accelerometer, length 20 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed
0ACC0500.01-1 Cable for accelerometer, length 50 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed
0ACC1000.01-1 Cable for accelerometer, length 100 m, 2x 0.34 mm², female M12 connector on the sensor side, can be used in cable drag chains, UL listed
Sensors
0ACS100A.00-1 Accelerometer, nominal sensitivity 100 mV/g, top exit
0ACS100A.90-1 Accelerometer, nominal sensitivity 100 mV/g, side exit

Vyberte prosím zemi a jazyk