1.4.3.0 * 14.03.2024 4 MB EXE AS4_HW_X20CM0985-02.exe
Popis V4.2 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02

Version 1.4.3.0:

ID: 783310
Bug fix by splitting the data point ConfigOutput11_12 into ConfigOutput11 and ConfigOutput12
If ConfigOutput12 has a negative value, it will be overwritten in the initscript. By separating ConfigOutput11_12 into ConfigOutput11 and ConfigOutput12,this is prevented and all values ​​are adopted correctly.
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(106)

Version 1.4.1.0:

ID: 721730
Value area extension for unbalanced load constant current asymmetry (K2).
A range of values ​​from 8 to 35 (0.08 to 0.35) is possible
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\62501_1.fw(106)

Version 1.4.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.3.0.0:

ID: 688200 / Support ID: 400268833, 400284558
Configuration parameter implemented to deactivate the evaluation of the current inputs if the generator voltages are missing
This prevents a noise at the current inputs being evaluated and leading to incorrect measured values,e.g. when the generator is not connected
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 688210 / Support ID: 400294065
Frequency measurement improved
Plausibility check is more robust against saddle-shaped signals in the areaof the zero crossing.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688215 / Support ID: 400305545
Problem at startup of the X2X fixed
X2X telegrams are no longer forwarded too early to subsequent X2X slaves during the startup phase. Thus, it is no longer possible for a mismatched FW to be loaded to the subsequent X2X slave.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688220 / Support ID: 400316271
Uneven load monitoring adapted for high unbalanced load currents
With unbalanced load currents above 4 times the nominal current, a fault isno longer immediately output
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688225
additional continuous current tripping characteristics
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 690330
Module documentation revised
Data sheet V 1.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(105)

Version 1.2.0.0:

ID: 666915
Adaptations for Automation Studio 4.8
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 674335
Units adapted for display in AS
Channel description changed: No
Configurationdescription changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.1.0.0:

ID: 646225 / Support ID: 400288465
If the "Over- and undervoltages check method" is configured to "Line voltages" or "Phase and line voltages", the "Over voltage of one phase" configurationis incorrectly used for generator monitoring for "Over voltage 2 of one phase".
Before using this upgrade, it is therefore necessary to check the correct configuration of "Over voltage 2 of one phase" for generator monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 653970
Module documentation revised
Data sheet V1.02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.4.1.0 * 06.09.2021 4 MB EXE AS4_HW_X20CM0985-02.exe
Popis V4.2 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02-02

Version 1.4.1.0:

ID: 721730
Value area extension for unbalanced load constant current asymmetry (K2).
A range of values ​​from 8 to 35 (0.08 to 0.35) is possible
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes
Firmware: 1\62501_1.fw(106)

Version 1.4.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed: yes
Firmware changed: no

Version 1.3.0.0:

ID: 688200 / Support ID: 400268833, 400284558
Configuration parameter implemented to deactivate the evaluation of the current inputs if the generatorvoltages are missing
This prevents a noise at the current inputs being evaluated and leading to incorrect measured values, e.g. when the generator is not connected
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 688210 / Support ID:400294065
Frequency measurement improved
Plausibility check is morerobust against saddle-shaped signals in the area of the zero crossing.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688215 / Support ID: 400305545
Problem at startup of the X2X fixed
X2X telegrams are no longer forwarded too early to subsequent X2X slaves during the startup phase. Thus, it is no longer possible for a mismatched FW to be loaded to the subsequent X2X slave.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688220 / Support ID: 400316271
Uneven load monitoring adapted for high unbalanced load currents
With unbalancedload currents above 4 times the nominal current, a fault is no longer immediately output
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688225
additional continuous current tripping characteristics
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 690330
Module documentation revised
Data sheet V 1.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(105)

Version 1.2.0.0:

ID: 666915
Adaptations for Automation Studio 4.8
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 674335
Units adapted for display in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.1.0.0:

ID: 646225 / Support ID: 400288465
If the "Over- and undervoltages check method" is configured to "Line voltages" or "Phase and line voltages", the "Over voltage of one phase" configuration is incorrectly used for generator monitoring for "Over voltage 2 of one phase".
Before using this upgrade, it is therefore necessary to check the correct configuration of "Over voltage 2 of one phase" for generator monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 653970
Module documentation revised
Data sheet V1.02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.4.0.0 * 23.07.2021 3 MB EXE AS4_HW_X20CM0985-02.exe
Popis V4.2 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02-02

Version 1.4.0.0:

ID:
Adaptations for Automation Studio 4.11
Channel description changed: no
Configuration description changed:yes
Firmware changed: no

Version 1.3.0.0:

ID: 688200 / Support ID: 400268833, 400284558
Configuration parameter implemented to deactivate the evaluation of the current inputs if the generator voltages are missing
This prevents a noise at the current inputs being evaluated and leading to incorrect measured values, e.g. when the generator is not connected
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 688210 / Support ID: 400294065
Frequency measurement improved
Plausibility check is more robust against saddle-shaped signals in the areaof the zero crossing.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688215 / Support ID: 400305545
Problem at startup of the X2X fixed
X2X telegrams are no longer forwarded too early to subsequent X2X slaves during the startup phase. Thus, it is no longer possible for a mismatched FW to be loaded to the subsequent X2X slave.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688220 / Support ID: 400316271
Uneven load monitoring adapted for high unbalanced load currents
With unbalanced load currents above 4 times the nominal current, a fault isno longer immediately output
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688225
additional continuous current tripping characteristics
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 690330
Module documentation revised
Data sheet V 1.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(105)

Version 1.2.0.0:

ID: 666915
Adaptations for Automation Studio 4.8
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 674335
Units adapted for display in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.1.0.0:

ID: 646225 / Support ID: 400288465
If the "Over- and undervoltages check method" is configured to "Line voltages" or "Phase and line voltages", the "Over voltage of one phase" configuration is incorrectly used for generator monitoring for "Over voltage 2 of one phase".
Before using this upgrade, it is therefore necessary to check the correct configuration of "Over voltage 2 of one phase" for generator monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 653970
Module documentation revised
Data sheet V1.02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.3.0.0 * 28.05.2020 3 MB EXE AS4_HW_X20CM0985-02.exe
Popis V4.2 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02

Version 1.3.0.0:

ID: 688200 / Support ID: 400268833, 400284558
Configuration parameter implemented to deactivate the evaluation of the current inputs if the generator voltages are missing
This prevents a noise at the current inputs being evaluated and leading to incorrect measured values, e.g. when the generator is not connected
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: Yes

ID: 688210 / Support ID: 400294065
Frequency measurement improved
Plausibility check is more robust against saddle-shaped signals in the areaofthe zero crossing.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688215 / SupportID: 400305545
Problem at startup of the X2X fixed
X2X telegrams areno longer forwarded too early to subsequent X2X slaves during the startup phase. Thus, it is no longer possible for a mismatched FW to be loaded to the subsequent X2X slave.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688220 / Support ID: 400316271
Uneven load monitoring adapted for high unbalanced load currents
With unbalanced load currents above 4 times the nominal current, a fault isno longer immediately output
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 688225
additional continuous current tripping characteristics
Channel description changed: No
Configuration description changed: Yes
Firmware changed: Yes

ID: 690330
Module documentation revised
Data sheet V 1.05
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(105)

Version 1.2.0.0:

ID: 666915
Adaptations for AutomationStudio 4.8
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 674335
Units adapted for display in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.1.0.0:

ID: 646225 / Support ID: 400288465
If the "Over- and undervoltages check method" is configured to "Line voltages"or "Phase and line voltages", the "Over voltage of one phase" configurationis incorrectly used for generator monitoring for "Over voltage 2 of one phase".
Before using this upgrade, it is therefore necessary to check the correct configuration of "Over voltage 2 of one phase" for generator monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 653970
Module documentation revised
Data sheet V1.02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.2.0.0 * 08.01.2020 3 MB EXE AS4_HW_X20CM0985-02.exe
Popis V4.2 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02

Version 1.2.0.0:

ID: 666915
Adaptations for Automation Studio 4.8
Channel description changed: Yes
Configuration description changed: Yes
Firmware changed: No

ID: 674335
Units adapted for display in AS
Channel description changed: No
Configuration description changed: Yes
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.1.0.0:

ID: 646225 / Support ID: 400288465
If the "Over- and undervoltages check method" is configured to "Line voltages" or "Phase and line voltages", the "Over voltage of one phase" configuration is incorrectly used for generator monitoring for "Over voltage 2 of one phase".
Before using this upgrade, it is therefore necessary to check the correct configuration of "Over voltage 2 of one phase" for generator monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 653970
Module documentation revised
Data sheet V1.02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.1.0.0 * 17.07.2019 3 MB EXE AS4_HW_X20CM0985-02.exe
Popis V4.2 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02

Version 1.1.0.0:

ID: 646225 / Support ID: 400288465
If the "Over- and undervoltages check method" is configured to "Line voltages" or "Phaseand line voltages", the "Over voltage of one phase" configurationis incorrectly used for generator monitoring for "Over voltage 2 of one phase".
Before using this upgrade, it is therefore necessary to check the correct configuration of "Over voltage 2 of one phase" for generator monitoring.
Channel description changed: No
Configuration description changed: No
Firmware changed: Yes

ID: 653970
Module documentation revised
Data sheet V1.02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(103)

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)
Verze Jazyk
Operační systém
Datum
Velikost
Typ Stáhnout
1.0.0.0 * 07.11.2018 3 MB EXE AS4_HW_X20CM0985-02.exe
Popis V4.2 HW Upgrade (X20CM0985-02)

Revision information X20CM0985-02

Version 1.0.0.0:

ID: 618420
support for X20CM0985-02
Channel description changed: No
Configuration description changed: No
Firmware changed: No
Firmware: 1\62501_1.fw(102)